PRODUCT CATALOG

The PFC6 series is the ideal economical choice for basic emergency lighting. The one piece unit body is injection molded using color stable, high impact UL 94-5V rated polycarbonate material. Emergency output is provided from two internally molded heads, with flush molded prismatic lenses. No external heads are visible, providing a slim, almost invisible profile. The PFC6 unit provides 6 volt output, ranging from 10 through 15 watts rated for 90 minutes. Unit can be wall or ceiling mounted.
  • Thermoplastic Injection Molded
  • Emergency Unit
  • Internal Molded heads
  • 6 Volt

Voltage

N/A 6 V

Wattage

N/A 15 W

Options

N/A Voltmeter

Accessories

N/A Vandal Bubble

N/A

  • Dual voltage input, 120/277 VAC. Contact factory for other voltages.
  • Line latching.
  • Constant current solid state voltage limited charger.
  • Solid state transfer switching.
  • Circuit design includes brownout protection, low voltage battery disconnect, and short circuit protection.
  • Circuit board includes momentary test switch and AC On visual indicator.

N/A

  • Injection molded of polycarbonate, high impact UL 94-5VA material.
  • Housing color will not vary with prolonged exposure to UV radiation.
  • Standard finish is white.
  • Universal J-box mounting pattern.
  • Unit can be wall or ceiling mounted. Keyhole mounting slots are provided.
  • All components are of snap-fit construction.
  • Housing includes cutout for surface mounted conduit use.
  • All electronic components, including Lead Calcium batteries, are pre-wired and assembled onto internal wire way chassis.
  • Minimal installation wiring is needed.

N/A Lamp Heads:

  • Lamp heads are molded flush to the housing. No external head assembly is visible. Front lens assembly is injection molded from crystal clear acrylic with precision molded linear spread pattern for efficient lumen output.
  • Emergency lamp output can be directed either horizontally or straight down by reversing the prismatic lens covers.
Battery:
  • Sealed maintenance free Lead Calcium, recombinant cell.
  • The battery is protected from deep discharge by a low voltage disconnect circuit.
  • 90 minutes minimum discharge.
Lamps:
  • Emergency lamp heads use wedge base, T5, tungsten high lumen output. Standard unit utilizes 5.4watt heads.
Listing/Code Compliance:
  • UL 924 listed
  • Life Safety NFPA 101,NEC/OSHA.
  • UL Damp location listed.
Warranty:
  • Battery, 5 year pro-rata
  • Charger board, 5 years

N/A Charge Mode (Fully Discharged Battery)

PFC6-10 Series (Lead Calcium Battery)

Unit Input (VAC) Input Current (mA) Power (Watts)
FFC6-10 120 40 44
FFC6-10 277 23 67


Note: Figures based on fully discharged battery on high charge.